BasicLine BL 541/542

Loop-Powered Isolator for Standard Signals

Extremely compact, accurate, reliable. This loop-powered isolator requires no external power source whatsoever – while ensuring the best quality, of course.

Facts

  • Loop-powered: a separate power supply is not required
  • Wiring effort reduced by 1/3
  • Full-fledged, galvanicaly isolated 1:1 transmission of 20mA signals
  • 2 channels on 6-mm mounting rail: it couldn’t be more compact
  • 1- and 2-channel versions avaliable
  • 0.2% full scale accuracy
  • Low voltage drop of 1.7 V
  • CE compliant and UL approved
  • 3-year warranty
  • Perfect price-performance ratio
Variants: BL 541, 1 channel BL 542, 2 channels
Input 0 … 20 mA
4 … 20 mA
2 x 0 … 20 mA
2 x 4 … 20 mA
Accuracy < 0.2 % full scale
Test voltage 1.5 kV AC
Working voltage 300 V AC/DC
Working voltage Loop-powered
Power supply Low voltage drop of 1.7 V
less

Downloads

Language:
Category:

Catalog Excerpts

Catalog Excerpt (en)

700 |  BasicLine BL 541/542
Product Description | Specifications | Product Range
PDF (file size: 0.47 MB)

Manuals

Manual (en)

704 |  BasicLine BL 541/542
PDF (file size: 1.04 MB)

Certificates / Approvals

EU Declaration of Conformity (en)

14302 |  BasicLine Types BL 510, BL 530, BL 541, BL 542, BL 560
Document No. EU181113A | 2018-11-13
PDF (file size: 0.45 MB)

Certificate of Compliance (UL) (en)

11548 |  BasicLine BL 541/542
Document No. 20130821-E220033; 2013/08/21
PDF (file size: 0.39 MB)

TR Declaration EAC (en)

12727 |  ProLine Devices
PDF (file size: 1.31 MB)

Software

Software (en)

11879 |  Datasheet for ePLAN P8 Product Macros
PDF (file size: 0.77 MB)

Software (en)

12437 |  ePLAN P8 Product Macros
ZIP (file size: 14.77 MB)